UPS COVER MY 30K

COVER Online Double-Conversion uninterruptible power supply, 30kVA/30kW. Tower cabinet without batteries. Capable of installing up to 80 x 9Ah batteries. 3:3/3:1 phase configuration.

11-MY00-0300

CHARACTERISTICS

  • True OnLine technology Double Conversion provides excellent output voltage performance regardless of power interference and the type of consumers being powered.
  • IGBT rectifier The most advanced technology providing very low THDi and high power factor.
  • Automatic bypass - uninterruptible Provides uninterrupted power to consumers in critical situations like overheating or failure.
  • Service bypass allows servicing of equipment without shutting down the powered loads. Separate power supply of the Bypass track gives the possibility to provide a backup power source for the consumers even in case of equipment failure or UPS protection tripping in the main track.
  • Communication:
  • RS485, ModBus for monitoring the operation of the power supply.
  • DryContact in/out relay contacts for interfacing with BMS systems,
  • SNMP integration with NMS-type network management systems,
  • Remote Emergency Power Off connector (REPO) for providing remote disconnection of power supply to consumers in case of fire,
  • Fire Protection Switch. (EPO) on the control panel allows you to immediately disconnect power from the consumers,
  • Touch control and monitoring panel gives the possibility to diagnose the parameters and operation mode of the power supply and allows logging of events. Available languages include Polish, English, Italian, Spanish, Russian, etc.
  • Small dimensions, so that no large space is required to install the unit. Power packing of 120 kW/m2.
  • High efficiency of the device 96% reduces the unit's own losses and limits the emitted heat, making the eventual cooling of rooms simpler and cheaper.
  • Tryb ECO mode (HE) allows a significant reduction in the cost of operation of the device and virtually eliminates heat emission. Programmable time periods during which the UPS operates in ECO mode, such as night time.
  • Configurable number of batteries 24-40 units and charging current allows for precise selection of the required autonomy time and the discontinuous battery charging function optimizes the life of the batteries used.
  • 3:3 or 3:1 output configuration allows you to adjust the number of outputs depending on the receiving system and the way you power your consumers.
  • Self-Aging Function allows you to test the device with a full load, even without connected consumers.
  • Automatic diagnostics with FTM (Fault Trace Management) function and fully digital control (32 bit DSP x2) guarantees full efficiency of the device, control of components and operating parameters without user intervention.
  • High value of input power factor ogranicza wartość prądu pobieranego przez urządzenie z sieci.
  • Maximum output power factor PF=1 delivers 20% more active power than standard solutions with PF=0.8.
  • Maximum wide input voltage range -60% ÷ +25% in normal operation mode ensures stable operation of the device without the need for batteries, which significantly extends their life.
  • Wide input frequency range in normal operation mode allows the power supply to be used freely in a network with unstable parameters and when powered by a generator set.
  • Ease of use The ease of connection to the network and the simple switching on and off of the device does not require special qualifications from the user.
  • Advanced battery management with "restart" function guarantees optimum charging and utilization of battery banks, increases battery life and reduces operating costs.
  • Excellent output voltage quality Achieved through the use of an IGBT inverter using highly advanced PWM control technology, a voltage with stable parameters is delivered, regardless of power disturbances and the type of powered devices.
  • High overload capacity ensures protection of the device and continuity of power supply in the presence of transient transients, and reduces the need to oversize the device in relation to the power of the consumers.
  • Advanced software enabling the user to have full control over the device and the powered loads.
  • Configurability of operating parameters nominal voltages, frequencies, preferred modes of operation, method of communication - greatly expands the range of possible applications.
  • Redundant configurations:
  • - Redundant parallel operation for increased reliability
  • - Capacitive parallel operation for increased power
  • - HotStandby operation (separated power supply for rectifier and bypass)

TECHNICAL SPECIFICATIONS

Model MY 30K
Power factor 30kVA / 30kW
Phases In/Out 3:3 / 3:1
Design Tower
Input
Nominal voltage 380 / 400 / 415 Vac
Voltage range -25% ÷ +25% @ 100% load
-65% ÷ +25% @ obciążenie ograniczone 15÷100%
Nominal frequency 50 / 60Hz
Frequency range -20% ÷ +20%
THDi <3%
Input power factor ≥0,99
Output
Nominal voltage 220 / 230 / 240 VAC | 380 / 400 / 415 Vac
Power factor 1,0
Voltage regulation statis/dynamic ±1% / ±3%
Nominal frequency 50 / 60 ± 0,1 Hz
Overload caability 105% - no limit; 115% - 60 min., 130% - 10 min., 155% - 60 sec., >155% - 200msec.
Efficiency in OnLine mode 96%
Efficiency in ECO mode 98%
Crest factor 3:1
Switching time 0ms
Batteries
Cold start yes
Type of batteries VRLA, AGM, gel
Batteries range 32 - 40 pcs x 12V
Max quantity of internal batteries 80 pcs x 9Ah
Max charging curent 20A
Charging type 3 – 8 hours up to 90% capacity (configurable)
Charging cycle According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control.
Dimensions and weights
Dimensions (S x G x W) 300 x 834 x 1250mm
Weight w/o batteries 85,0 kg
Weight with batteries 301,0 kg
Signaling and communication ports
Operating status indicator LCD 4,3'' + alarm dźwiękowy
Communication 2 x Smart Slot na dodatkowe karty komunikacyjne, REPO (NC), 5 x Dry Contact Out, 1 x Dry Contact In, RS485 -Modbus RTU.
Environmental conditions
Noise level <50 dB @ load 100%
Operating temperature for UPS 0°C ÷ 40°C
Recommended operating temperature 15 °C ÷ 25 °C
Storage temperature -25°C ÷ 55°C
Humidity 0 ÷ 95% (non-condensing)
Cerifications
Interference immunity EN 62040-2:2016
Safety IEC62040-1-2 :2017, CE
Optional accesories
- SNMP card
- Karta AS400 (dry-contact)
- Environmental sensor (EMD)
- Remote Emergency Power Off button
- External maintenance bypass
- Parallel cards
- Remote LCD panel
- Backfeed protection

Due to constant product improvement all specifications are subject to change without notice.

Apparent power [kVA]
30
Active power [kW]
30
Technology:
VFI-SS-111 (OnLine DoubleConversion)
Phase In/Out:
3:3
Output PF:
1
Max internal batteries
80

Related Products ( 16 other products in the same category )