• Pack

COVER PS 20K + 2 x PS EBM (20x9Ah)

COVER CORE PS 20K 20kVA/kW UPS with two EBM PS battery modules (20x9Ah).

UPS can be configured as 3/3; 3/1; 1/1 and 1/3.

Total number of installed batteries 40 x 9Ah.

Height of the set 9U.

11-Z-PS 20K-240009

BACKUP TIME

EBM PS Load Backup time [min]
PS 20K
UPS +2xEBMs (40x9Ah) 100% 4
75% 7
50% 12
25% 29

TECHNICAL SPECIFICATIONS

Model PS 20K
Power factor 20kVA / 20kW
Phases In/Out 3:3
Design Rack/Tower
Input
Nominal voltage 220 / 230 / 240 VAC | 380 / 400 / 415 Vac
Voltage range 100 ÷ 160 VAC @ load 50% - 100%, 160 ÷ 300 VAC @ load 100%
174 ÷ 278 VAC @ load 50% - 100%, 278 ÷ 522 VAC @ load 100%
Nominal frequency 50 / 60Hz
Frequency range 45 ÷ 65 Hz
THDi <3%
Input power factor ≥0,99
Output
Nominal voltage 220 / 230 / 240 VAC | 380 / 400 / 415 Vac
Power factor 1,0
Voltage regulation statis/dynamic ±1% / ±3%
Nominal frequency 50 / 60 ± 0,1 Hz
Overload caability 105% no limit, 125% - 10 min., 150% - 30 s., >150% - 500 ms
Efficiency in OnLine mode 96%
Efficiency in ECO mode 98%
Crest factor 3:1
Switching time 0ms
Batteries
Cold start yes
Type of batteries VRLA, AGM, gel
Batteries range 32 - 40 pcs x 12V
Max charging curent 13A
Charging type 3 – 8 hours up to 90% capacity (configurable)
Charging cycle According to DIN 41773 with automatic charging shutdown according to current and voltage criteria, with time control.
Dimensions and weights
Dimensions (S x G x W) 440 x 680 x 132 (3U)
Weight w/o batteries 32,0 kg
Signaling and communication ports
Operating status indicator LCD + audible alarm
Communication USB, RS232, RS485, Dry in/out, EMBS, EPO, slot SNMP
Environmental conditions
Noise level <65 dB @ load 100%
Operating temperature for UPS 0°C ÷ 40°C
Recommended operating temperature 15 °C ÷ 25 °C
Storage temperature -20°C ÷ 40°C
Humidity 0 ÷ 95% (non-condensing)
Cerifications
Interference immunity EN 62040-2:2018, EN 61000-3-2:2019, EN 61000-3-3:2013+A1:2019
Safety EN 62040-1:2019, EN 62040-1-2:2003, 62040-3:2001, CE
Optional accesories
- SNMP card
- AS 400 mini (dry-contact) card
- Environmental sensor (EMD)
- Remote Emergency Power Off button
- External maintenance bypass
- Remote LCD panel

Due to constant product improvement all specifications are subject to change without notice.